| Technical Specifications |
5000 |
| Rating (kVA/kW) |
5 kVA / 4.5 kW |
| Paralleling |
| Maximum rating / redundancy1 |
10 kVA / 5 kVA + 5 kVA redundancy |
| Inputs |
| Technology |
VFI-SS-113, on-line double conversion
with power factor correction, convection cooled static bypass switch |
| Number of phases, input connections |
L + N, terminals up to 6 mm2 |
| Nominal voltage |
200/208/220/230/240/250 V |
| Voltage range without using battery2 |
120 - 280 V |
| Input frequency range, THDI |
40-70 Hz, < 7% |
| Outputs |
| Output connections3 |
Terminals + 8 IEC C13 (10A) +
2 IEC C19 (16A) |
| Remotely controlled Powershare sockets |
2 groups (2 IEC C13 10A per group) |
| Output voltage and frequency4,
THDU, efficiency5 |
200/208/230/240 /250 V, 50 / 60
Hz autoselect, frequency converter as standard, < 2%, 97% |
| Backup time6 |
| Eaton MX standard backup time |
8 minutes |
| Eaton MX + EXB / MX + 2 EXB / MX + 3 EXB |
35 / 60 / 95 minutes |
| Communications |
| Slots |
1 slot (MX) or 2 slots (MX Frame) for Network
Management Card, NMC ModBus/JBus card or MC Contacts/Serial card |
| Ports |
Remote Power off (RJ11), 5 output contacts
(DB9), setup using Solution-Pac8
, (USB and DB9-serial ports), EXB module detection (RJ45), paralleling (DB
15) |
| Operating conditions, standards and approvals |
| Performance, safety, EMC, surge protection |
IEC/EN 62 040-3, IEC/EN 62 040-1-1, IEC/EN
62 040-2 class A (class B as option), 4 kV IEC 61 643, UL 1778 and CSA 22.29 |
| Operating temperature, noise, approvals, guarantee |
0°C to 40°C continuous, 45 dbA10,
UL, TüV, GS mark, CB, C-Tick, CE, IEC 61 931, one year11 |
| Dimensions H x W x D / Weight |
| Eaton MX standard backup tower |
444.5 mm x 130.6 mm x 735 mm / 57 kg |
| Eaton MX standard backup rack |
3U x 444.5 mm wide compatible with 800-1000
mm deep rack |
| Eaton MX EXB battery unit tower / rack |
444.5 mm x 130.6 mm x 650 mm / 3U x 444.5 mm
wide / 70 kg |
| Eaton MX ModularEasy, paralleling kit |
Dimensions same as EXB battery unit / 10 kg |